Sizing a motor branch circuit under NEC Article 430
Motor circuits do not follow the ordinary breaker-equals-wire rule. Conductors, short-circuit protection and overloads are each sized from a different current and a different percentage. This guide puts the steps in order, with worked examples and a 460 V reference table.
Two currents: table FLC and nameplate
The most common error in motor work is using the wrong current. NEC 430.6(A)(1) says that conductors, switches, and branch-circuit short-circuit and ground-fault protection are sized from the full-load current in the NEC tables, not from the motor nameplate. Overload protection, on the other hand, is sized from the nameplate current (430.6(A)(2) and 430.32).
| Motor type | Full-load current table |
|---|---|
| Single-phase AC | Table 430.248 |
| Two-phase AC (4-wire) | Table 430.249 |
| Three-phase AC, induction and wound-rotor | Table 430.250 |
| Three-phase synchronous, unity power factor | Table 430.250, synchronous columns (× 1.1 at 90% PF, × 1.25 at 80% PF) |
A few values from those tables: a 5 hp single-phase motor at 230 V is 28 A; a 10 hp three-phase motor at 460 V is 14 A; a 25 hp synchronous motor at 575 V and unity power factor is 21 A; a 7-1/2 hp two-phase motor at 460 V is 9 A.
Step 1: branch-circuit conductors (430.22)
Conductors supplying a single continuous-duty motor need an ampacity of at least 125% of the table full-load current.
Minimum ampacity = 1.25 × table FLC 10 hp, 460 V, three-phase: 1.25 × 14 A = 17.5 A
Then choose a conductor from Table 310.16 using the column that matches the terminal temperature rating of the equipment (60 °C unless the equipment is marked 75 °C, for circuits of 100 A or less), and apply any ambient or bundling correction before comparing.
Step 2: short-circuit and ground-fault protection (430.52)
The branch-circuit breaker or fuse protects against short circuits and ground faults only, so it is allowed to be far larger than the conductor ampacity; the overloads protect the motor and wire from overheating. Table 430.52 gives the maximum setting as a percentage of table FLC:
| Device | Maximum % of FLC |
|---|---|
| Non-time-delay fuse | 300% |
| Dual-element (time-delay) fuse | 175% |
| Instantaneous-trip breaker | 800% |
| Inverse-time breaker | 250% |
Design B energy-efficient motors allow 1,100% for instantaneous-trip breakers; wound-rotor and DC motors have much lower limits (150% for fuses and inverse-time breakers). Instantaneous-trip breakers are only permitted as part of a listed combination motor controller.
If the percentage does not land on a standard rating, Exception No. 1 permits the next higher standard size. 10 hp at 460 V: inverse-time breaker 14 × 2.5 = 35 A, a standard size, so 35 A; dual-element fuse 14 × 1.75 = 24.5 A, next standard size 25 A. Exception No. 2 allows more if the motor will not start, within stated ceilings.
Step 3: overload protection (430.32)
Separate overload devices for a continuous-duty motor over 1 hp are sized from the nameplate full-load current:
- Motors with a marked service factor of 1.15 or more, or a marked temperature rise of 40 °C or less: not more than 125% of nameplate current.
- All other motors: not more than 115%.
Example: nameplate 48 A, service factor 1.15: 48 × 1.25 = 60 A maximum. With a service factor of 1.0 the limit is 48 × 1.15 = 55.2 A. If the selected relay trips during normal starting, the code allows a higher setting up to 140% and 130% respectively.
Step 4: motors that do not run continuously (Table 430.22(E))
For motors on short-time, intermittent, periodic or varying duty, conductors are sized as a percentage of the nameplate current from Table 430.22(E):
| Duty | 5-min rated | 15-min rated | 30 and 60-min rated | Continuous rated |
|---|---|---|---|---|
| Short-time (valves, raising rolls) | 110% | 120% | 150% | — |
| Intermittent (elevators, freight lifts) | 85% | 85% | 90% | 140% |
| Periodic (rolls, ore and coal machinery) | 85% | 90% | 95% | 140% |
| Varying | 110% | 120% | 150% | 200% |
Example: a 7.5 hp, 460 V, 15-minute rated motor on varying duty with a nameplate current of 11.1 A needs conductors of at least 11.1 × 1.20 = 13.32 A. The 125% rule of 430.22 does not apply to it.
Step 5: several motors on one conductor (430.24)
Conductors supplying several motors need an ampacity of at least 125% of the full-load current of the largest motor plus the full-load currents of all the others, plus any other loads on the same conductors.
Two motors with FLCs of 28.9 A and 47.8 A: 1.25 × 47.8 + 28.9 = 88.65 A. A 25 hp and a 10 hp motor at 460 V (34 A and 14 A): 1.25 × 34 + 14 = 56.5 A.
If two motors are the same size, only one of them is taken at 125%.
Reference: 460 V three-phase induction motors
| hp | FLC (A) | Conductors ≥ (A) | Inverse-time breaker (A) | Dual-element fuse (A) |
|---|---|---|---|---|
| 1 | 2.1 | 2.63 | 15 | 15 |
| 2 | 3.4 | 4.25 | 15 | 15 |
| 3 | 4.8 | 6 | 15 | 15 |
| 5 | 7.6 | 9.5 | 20 | 15 |
| 7-1/2 | 11 | 13.75 | 30 | 20 |
| 10 | 14 | 17.5 | 35 | 25 |
| 15 | 21 | 26.25 | 60 | 40 |
| 20 | 27 | 33.75 | 70 | 50 |
| 25 | 34 | 42.5 | 90 | 60 |
| 30 | 40 | 50 | 100 | 70 |
| 40 | 52 | 65 | 150 | 100 |
| 50 | 65 | 81.25 | 175 | 125 |
| 60 | 77 | 96.25 | 200 | 150 |
| 75 | 96 | 120 | 250 | 175 |
| 100 | 124 | 155 | 350 | 225 |
The protective-device columns are maximums for the branch circuit. Smaller devices are fine as long as the motor starts and runs without nuisance tripping.
Common mistakes
- Sizing conductors or the breaker from the nameplate. Both use the table FLC; only overloads use the nameplate.
- Sizing the breaker at 125% like the wire. Table 430.52 allows up to 250% for an inverse-time breaker because the overloads do the overload job.
- Using the 230 V column for a 208 V system. Use the column for the actual system voltage; Table 430.250 has separate 200 V and 208 V columns.
- Applying 125% to every motor in a group. Only the largest motor is taken at 125% under 430.24.
- Using 430.22 for a 15-minute rated motor. Duty-cycle motors use Table 430.22(E) and the nameplate current.
Questions people ask
What is the minimum conductor ampacity for two motors of 28.9 A and 47.8 A?
125% of the larger plus 100% of the smaller: 1.25 × 47.8 + 28.9 = 88.65 A (430.24).
What is the full-load current of a 25 hp, 575 V synchronous motor at unity power factor?
21 A from the synchronous columns of Table 430.250. At 90% power factor multiply by 1.1, at 80% by 1.25.
A 7.5 hp, 460 V, 15-minute rated motor on varying duty has a nameplate current of 11.1 A. What is the minimum branch-circuit ampacity?
Table 430.22(E), varying duty, 15-minute rating: 120% of nameplate, 11.1 × 1.2 = 13.32 A.
Can the branch-circuit breaker be bigger than the wire ampacity?
Yes, for motor circuits. Table 430.52 sets the maximum for short-circuit and ground-fault protection as a percentage of FLC (250% for an inverse-time breaker), while separate overload protection sized by 430.32 protects against overheating.
Sources
- NFPA 70, National Electrical Code (free read-only access): Article 430 (430.6, 430.22, 430.24, 430.32, 430.52; Tables 430.22(E), 430.248–430.250)
- Open Exam Prep, motor nameplate vs. table FLC and conductor sizing (Table 430.22(E) reproduced)
- Open Exam Prep, motor overload and branch-circuit protection (430.32 and Table 430.52 reproduced)
- Full-load current tables: our motor FLC calculator data, checked against a printed NEC table scan and two independent reproductions (see Sources & methodology)
Found a mistake or an outdated value? Email contact@alljobscalc.com and we will check it against the source and correct it.