NEC Article 430 Part XIV full-load current lookup by horsepower and voltage: Table 430.248 (single-phase), 430.249 (two-phase) and 430.250 (three-phase, including synchronous motors at unity, 90% and 80% power factor), with the 125% branch-circuit conductor sizing rule applied.

Full-load current (FLC)7.6 A
Min. conductor ampacity (125%)9.5 A

How this is calculated

NEC 430.6(A)(1) requires motor branch-circuit and feeder conductor sizing, overload protection, and short-circuit protection to be based on the table full-load current value for the motor's horsepower and voltage — not the motor's actual nameplate current, even if they differ. Tables 430.248, 430.249 and 430.250 give those standardized values for single-phase, two-phase and three-phase motors.

Min. conductor ampacity = FLC × 1.25  (NEC 430.22, single continuous-duty motor)

This 125% factor covers the single most common case: one continuous-duty motor on its own branch circuit. Multi-motor circuits, intermittent-duty motors, and overload/short-circuit protection device sizing (NEC 430.32, 430.52) follow different, motor-type-dependent rules not covered by this calculator.

Table 430.250 — Three-Phase (reference)

HP115V200V208V230V460V575V2300V
1/24.42.52.42.21.10.9—
3/46.43.73.53.21.61.3—
18.44.84.64.22.11.7—
1-1/2126.96.6632.4—
213.67.87.56.83.42.7—
3—1110.69.64.83.9—
5—17.516.715.27.66.1—
7-1/2—25.324.222119—
10—32.230.8281411—
15—48.346.2422117—
20—62.159.4542722—
25—78.274.8683427—
30—9288804032—
40—1201141045241—
50—1501431306552—
60—177169154776216
75—221211192967720
100—2852732481249926
125—35934331215612531
150—41439636018014437
200—55252848024019249
250————30224260
300————36128972
350————41433683
400————47738295
450————515412103
500————590472118
For estimation and reference only. This calculator covers table FLC lookup and single-motor branch-circuit conductor sizing only. Overload protection, short-circuit/ground-fault protection (which varies by motor design letter and starting characteristics), multi-motor circuits, and motor control center design all have additional NEC Article 430 rules not encoded here. Always verify against the current NEC edition and the motor's actual nameplate before sizing a real circuit.

In-depth guide: Sizing a motor branch circuit under NEC Article 430

How this calculator works

NEC Table 430.248 (single-phase), Table 430.249 (two-phase, 4-wire) and Table 430.250 (three-phase, including the synchronous-type unity power factor columns and the 1.1 / 1.25 footnote multipliers for 90% / 80% power factor) full-load current; 125% conductor sizing per NEC 430.22. European mode: I = P / (√3 × U × η × cos φ) with the IE3 minimum efficiencies of Commission Regulation (EU) 2019/1781, Annex I.

Worked example

A 10 hp three-phase motor at 460 V.

Table 430.250 gives a full-load current of 14 A. Branch-circuit conductors for a single continuous-duty motor must be at least 125% of that: 14 × 1.25 = 17.5 A minimum conductor ampacity.

The same 10 hp motor at 208 V draws 30.8 A from the table — about 2.2 times the current at 460 V, which is why larger motors are usually run at the higher voltage.

Frequently asked questions

Should I use the nameplate current or the table value?

For conductor sizing, short-circuit and ground-fault protection, NEC 430.6(A)(1) requires the table full-load current, not the nameplate. The nameplate current is used for sizing overload protection.

Why 125%?

NEC 430.22 requires branch-circuit conductors for a single continuous-duty motor to have an ampacity of at least 125% of the motor's full-load current, to cover starting and running heat.

What about 230 V motors on a 208 V system?

Use the column for the actual system voltage. A motor nameplated 208-230 V running on 208 V draws more current, so the 208 V column (or 200 V for some tables) gives the right value.

Does this size the breaker too?

No. Branch-circuit short-circuit and ground-fault protection follows NEC 430.52 and depends on the device type and motor design — it is often well above 125%.

What is the full-load current of a 25 hp, 575 V synchronous motor at unity power factor?

Using Part XIV of Article 430, Table 430.250 lists synchronous-type motors at unity power factor in separate columns: a 25 hp, 575 V synchronous motor has a full-load current of 21 A (26 A at 460 V, 53 A at 230 V). Its branch-circuit conductors need at least 21 × 1.25 = 26.25 A.

How do I find the full-load current of a synchronous motor at 90% or 80% power factor?

Take the unity-power-factor value from Table 430.250 and multiply it by 1.1 for 90% or 1.25 for 80%, as the table footnote requires. A 75 hp, 230 V synchronous motor is 155 A at unity, 170.5 A at 90% and 193.75 A at 80%.

Which table covers two-phase motors?

Table 430.249 (two-phase, 4-wire). A 7-1/2 hp, 460 V two-phase motor has a full-load current of 9.0 A. In a 2-phase, 3-wire system the common conductor carries 1.41 times the table value.

Common mistakes

  • Sizing wire or breaker from the nameplate. NEC 430.6(A)(1) requires the table full-load current for conductors and short-circuit protection. The nameplate current is for overloads.
  • Using the 230 V column on a 208 V system. Use the column for the actual system voltage. A 10 hp three-phase motor is 28 A in the 230 V column but 30.8 A in the 208 V column.
  • Forgetting the synchronous power-factor multiplier. The synchronous columns of Table 430.250 are for unity power factor. Multiply by 1.1 at 90% and by 1.25 at 80% power factor.
  • Sizing the breaker at 125%. The 125% rule is for conductors. Branch short-circuit protection follows Table 430.52 (up to 250% of FLC for an inverse-time breaker).

What it does not cover

Overload and short-circuit protection sizing, multi-motor circuits.

Sources