Home / Electrical / Wire & Breaker Ampacity
Electrical

Wire & Breaker Ampacity Calculator

NEC Table 310.16 allowable ampacity, corrected for ambient temperature and conductor bundling, with a suggested standard breaker size.

THHN/THWN-2 is typically 90°C rated, but terminals are often limited to the 60°C or 75°C column — see note below.
Base ampacity (4 AWG)85 A
Ambient correction factor× 1
Bundling adjustment factor× 1
Adjusted ampacity85.0 A
Suggested standard breaker80 A

How this is calculated

NEC Table 310.16 lists the base allowable ampacity for insulated copper and aluminum conductors under standard conditions (30°C ambient, no more than 3 current-carrying conductors in a raceway or cable). When real conditions differ, NEC 310.15 requires applying correction factors:

  • Ambient temperature correction (Table 310.15(B)(1)) — hotter environments reduce allowable ampacity.
  • Conductor bundling adjustment (Table 310.15(C)(1)) — more current-carrying conductors sharing a raceway reduce each conductor's heat dissipation, so ampacity is derated.

Adjusted ampacity = base ampacity × ambient factor × bundling factor

The 60°C/75°C terminal rating rule

Even if a conductor is rated 90°C (like most THHN/THWN-2), NEC 110.14(C) generally requires sizing based on the temperature rating of the terminals it lands on — commonly 60°C for equipment rated 100A or less, and 75°C above that, unless equipment is specifically listed for a higher rating. A 90°C conductor is often chosen for its higher ampacity headroom under derating, but the final circuit is still limited by the weakest-rated terminal in the circuit. This calculator shows the ampacity for the column you select — always cross-check against actual equipment terminal ratings.

For estimation and reference only. This calculator estimates conductor ampacity from published NEC Table 310.16 values and standard correction factors. It does not account for every NEC exception (e.g., specific equipment listings, continuous-load 125% sizing rules, or voltage-drop sizing). Always verify against the current NEC edition adopted in your jurisdiction and the equipment manufacturer's terminal ratings before sizing a real circuit.

In-depth guide: Voltage drop formula, with worked examples · Sizing a motor branch circuit under NEC Article 430

How this calculator works

NEC Table 310.16 (60 / 75 / 90 °C columns, copper and aluminum), ambient correction from 310.15(B)(1) and bundling adjustment from 310.15(C)(1).

Worked example

10 AWG copper THHN in the 90°C column, in a 10–15°C ambient, with no more than 3 current-carrying conductors.

Base ampacity from Table 310.16 is 40 A. The cool-ambient correction factor is 1.15, so the adjusted ampacity is 40 × 1.15 = 46 A, and the next standard breaker at or below that is 45 A.

Remember the terminal rule: if the breaker and device terminals are rated 60°C, the same 10 AWG wire is limited to its 60°C value of 30 A, no matter how cool the room is.

Frequently asked questions

How many amps can 12 AWG copper carry?

Table 310.16 lists 20 A at 60°C, 25 A at 75°C and 30 A at 90°C. In practice 12 AWG copper is protected at 20 A for general branch circuits because of the small-conductor rule in NEC 240.4(D).

Why use the 90°C column if terminals are only 60°C or 75°C?

The 90°C rating gives you a higher starting number to apply derating to (for heat or bundling). After derating, the result still cannot exceed the ampacity of the terminal temperature column — that is how the 90°C headroom gets used.

When do I have to derate for bundling?

When there are more than three current-carrying conductors in a raceway or cable. 4–6 conductors use 80%, 7–9 use 70%, and 10–20 use 50% of the base ampacity, per Table 310.15(C)(1).

Does this include the 125% continuous-load rule?

No. Continuous loads (3 hours or more) must be sized at 125% of the load before you compare against ampacity. Apply that first, then use this table to pick the conductor.

Common mistakes

  • Using the 90 °C column for the final answer. The 90 °C column is a starting point for derating. The result may not exceed the ampacity of the lowest-rated termination, usually 60 °C or 75 °C (NEC 110.14(C)).
  • Forgetting the small-conductor limits. NEC 240.4(D) caps the overcurrent protection of 14, 12 and 10 AWG copper at 15, 20 and 30 A in most cases, whatever Table 310.16 says.
  • Counting grounds as current-carrying. Equipment grounding conductors count for conduit fill but not for the bundling adjustment. A neutral that carries only the unbalanced current of a 3-wire circuit is not counted either.
  • Skipping the continuous-load step. A load that runs three hours or more is sized at 125% before you compare it with the conductor ampacity.

What it does not cover

The small-conductor breaker limits of NEC 240.4(D) and other overcurrent rules are flagged on the page, not fully modelled.

Sources

Last reviewed:

Related calculators

Embed this calculator

Free to use on your own website, blog, or training material — paste this code where you want the calculator to appear.