Home / Electrical / EMT Conduit Fill Chart
Electrical

EMT Conduit Fill Chart (THHN/THWN-2)

The most conductors of one size allowed in each EMT trade size, worked out from NEC Chapter 9 Tables 4 and 5 the same way Annex C Table C.1 is. Find your wire size on the left and read across.

Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1222356184138241364476608
12 AWG916264561101176266347443
10 AWG51016283863111167219279
8 AWG3691622366496126161
6 AWG147121626466991116
4 AWG1247101628435671
3 AWG113681324364760
2 AWG113571120304051
1 AWG11145815222937
1/0 AWG—1134712192532
2/0 AWG—1123610162026
3/0 AWG—111358131722
4/0 AWG——11147111418
250 kcmil——1113691115
300 kcmil———113571013

Rows are THHN/THWN-2 copper. A dash means even a single conductor of that size exceeds the 53% limit for that trade size. When a count works out to a fraction of 0.8 or more, it is rounded up (Chapter 9, Note 7).

EMT internal area and 40% fill

Chapter 9 Table 1 lets three or more conductors fill 40% of the conduit’s internal area. These are the areas the chart divides by.

Trade sizeTotal area40% fill area
1/2"0.304 in²0.122 in²
3/4"0.533 in²0.213 in²
1"0.864 in²0.346 in²
1-1/4"1.496 in²0.598 in²
1-1/2"2.036 in²0.814 in²
2"3.356 in²1.342 in²
2-1/2"5.858 in²2.343 in²
3"8.846 in²3.538 in²
3-1/2"11.545 in²4.618 in²
4"14.753 in²5.901 in²

How to read and use the chart

  • The counts are for one wire size and one insulation type at a time. For a mix of sizes, add up each conductor’s area instead.
  • One conductor may fill 53% of the conduit and two conductors 31%; three or more, 40%.
  • Equipment grounding conductors count toward fill like any other conductor.
  • Fill is only one limit: more than three current-carrying conductors in a raceway also reduce each one’s ampacity (Table 310.15(C)(1)).

For mixed wire sizes, use the conduit fill calculator.

For estimation and reference only. Computed from NEC Chapter 9 Table 4 (EMT) and Table 5 (THHN/THWN-2) areas. Other insulation types (XHHW, RHH, bare) have different areas, and local amendments can differ. Check the NEC edition your jurisdiction has adopted.

In-depth guide: Conduit fill rules: how NEC Chapter 9 sizes a raceway

Worked example

Three 12 AWG THHN conductors (a 20 A circuit with its ground) in 1/2" EMT.

Each 12 AWG THHN is 0.0133 in², so three take 0.0399 in². The 40% area of 1/2" EMT is 0.122 in², so they fit with room to spare; the chart shows 9 is the limit.

Going to 3/4" EMT raises the limit to 16 conductors of 12 AWG, enough for several circuits — remember to derate ampacity once more than three are current-carrying.

Frequently asked questions

How many 12 AWG wires can go in 3/4" EMT?

Sixteen THHN/THWN-2 conductors, from NEC Chapter 9 and Annex C Table C.1. For 14 AWG it is 22, and for 10 AWG it is 10.

How many wires in 1/2" EMT?

Twelve 14 AWG, nine 12 AWG, five 10 AWG or three 8 AWG THHN conductors.

Does the ground wire count in conduit fill?

Yes. Equipment grounding conductors count toward fill like any other conductor, using their own area.

Why does the 3-or-more limit drop to 40%?

More conductors mean more heat and harder pulls. Chapter 9 Table 1 sets 53% for one conductor, 31% for two and 40% for three or more.