Single-phase and three-phase voltage drop by wire size, current, and one-way circuit length, checked against the NEC's informational 3% and 5% guidance.

Distance from source to load, one direction — not round trip.
Voltage drop1.97 V
Percent drop1.64%
Voltage at load118.0 V
NEC guidance✅ Within 3% branch-circuit target

How this is calculated

This calculator uses the standard K-factor method taught for NEC exam prep and field use:

VD = (2 × K × I × D) ÷ CM  (single-phase)
VD = (1.732 × K × I × D) ÷ CM  (three-phase)

Where K is the resistivity constant (12.9 for copper, 21.2 for aluminum — approximate ohms·cmil/ft at typical operating temperature), I is load current in amps, D is one-way circuit length in feet, and CM is the conductor's circular-mil area from NEC Chapter 9, Table 8. The 2× (or 1.732× for three-phase) factor accounts for the full circuit, not just one leg.

For a more precise result, an estimator/engineer can instead use actual AC resistance and reactance values from NEC Chapter 9, Table 9, which account for conduit type and power factor — this K-factor method is a widely used simplified approximation, good for field estimating and most residential/light-commercial work.

NEC voltage drop guidance

NEC 210.19(A) and 215.2(A) include informational notes recommending voltage drop be limited to 3% for a branch circuit, and 5% total for branch circuit plus feeder combined. These are informational recommendations for efficient design, not enforceable code requirements — but exceeding them commonly causes dim lighting, motor overheating, and equipment that underperforms its rating.

AWG / kcmilCircular mils
14 AWG4,110
12 AWG6,530
10 AWG10,380
8 AWG16,510
6 AWG26,240
4 AWG41,740
3 AWG52,620
2 AWG66,360
1 AWG83,690
1/0 AWG105,600
2/0 AWG133,100
3/0 AWG167,800
4/0 AWG211,600
250 kcmil250,000
300 kcmil300,000
350 kcmil350,000
400 kcmil400,000
500 kcmil500,000
For estimation and reference only. This tool provides a planning estimate based on commonly published code tables and rules of thumb. It is not a substitute for a licensed professional, a stamped engineering calculation, or your local Authority Having Jurisdiction (AHJ). Code editions and local amendments vary — always verify against the current code adopted in your area before design, bidding, or installation.

In-depth guide: Voltage drop formula, with worked examples

How this calculator works

K-factor method: VD = 2 × K × I × D ÷ CM (×1.732 instead of 2 for three-phase), K = 12.9 copper / 21.2 aluminum; circular mils from NEC Chapter 9, Table 8; 3% / 5% guidance from the informational notes to NEC 210.19(A) and 215.2(A). Metric mode: simplified method of the Spanish Guía Técnica de Aplicación del REBT, Anexo 2 (e = 2·P·L/(γ·S·U) single-phase, P·L/(γ·S·U) three-phase, reactance neglected up to 120 mm², γ from its Table 3) and the REBT limits of its Table 6.

Maximum one-way distance for a 3% voltage drop (copper, single-phase)

Feet of one-way circuit length before the drop reaches 3%, using the same K-factor formula as the calculator above (K = 12.9 for copper). Longer runs need the next wire size up.

Wire · 120 V15 A20 A30 A40 A50 A
14 AWG38 ft28 ft19 ft14 ft11 ft
12 AWG60 ft45 ft30 ft22 ft18 ft
10 AWG96 ft72 ft48 ft36 ft28 ft
8 AWG153 ft115 ft76 ft57 ft46 ft
6 AWG244 ft183 ft122 ft91 ft73 ft
4 AWG388 ft291 ft194 ft145 ft116 ft
2 AWG617 ft462 ft308 ft231 ft185 ft
1/0 AWG982 ft736 ft491 ft368 ft294 ft
Wire · 240 V15 A20 A30 A40 A50 A
14 AWG76 ft57 ft38 ft28 ft22 ft
12 AWG121 ft91 ft60 ft45 ft36 ft
10 AWG193 ft144 ft96 ft72 ft57 ft
8 AWG307 ft230 ft153 ft115 ft92 ft
6 AWG488 ft366 ft244 ft183 ft146 ft
4 AWG776 ft582 ft388 ft291 ft232 ft
2 AWG1,234 ft925 ft617 ft462 ft370 ft
1/0 AWG1,964 ft1,473 ft982 ft736 ft589 ft

Worked example

A 20 A load on a 120 V single-phase circuit, 100 ft one-way, copper conductors.

12 AWG: VD = (2 × 12.9 × 20 × 100) ÷ 6,530 = 7.90 V, or 6.58% — well past the 5% total guidance. 10 AWG: 4.97 V (4.14%) — under 5% but still over the 3% branch target. 8 AWG: 3.13 V (2.60%) — within 3%, leaving about 116.9 V at the load.

So a run that is "only" a 20 A circuit can still need 8 AWG once the distance gets long, even though 12 AWG is enough for the ampacity.

Frequently asked questions

What is an acceptable voltage drop?

The NEC informational notes in 210.19(A) and 215.2(A) recommend no more than 3% on a branch circuit and 5% total for feeder plus branch circuit. They are design recommendations, not enforceable requirements, but most engineers and inspectors treat them as the target.

Do I use one-way or round-trip distance?

Enter the one-way distance from the source to the load. The formula already multiplies by 2 for single-phase (out and back) or by 1.732 for three-phase.

Why does aluminum show a bigger voltage drop than copper?

Aluminum has higher resistivity — K is about 21.2 versus 12.9 for copper — so the same size conductor drops roughly 64% more voltage. Aluminum runs are usually upsized one or two sizes to compensate.

Is the K-factor method accurate enough?

It is the standard simplified method for field estimating and most residential and light-commercial work. For long feeders or low power factor loads, engineers use the AC resistance and reactance values from NEC Chapter 9, Table 9 instead.

Common mistakes

  • Entering the round-trip length. Enter the one-way distance from the panel to the load. The single-phase formula already multiplies by 2 for the return conductor, so doubling it yourself counts the run four times.
  • Stopping at the ampacity check. A conductor that is big enough for the current can still drop too much voltage on a long run. A 20 A, 120 V circuit 100 ft long is fine on 12 AWG for ampacity but needs 8 AWG to stay within 3%.
  • Checking only the branch circuit. The NEC recommendation is 3% for a branch circuit or feeder and 5% for both together. A feeder that already drops 3% leaves only 2% for the branch circuits it serves.
  • Metric mode: using the 20 °C conductivity. The REBT guide's simplified method takes the cable at its maximum service temperature: 70 °C for PVC insulation, 90 °C for XLPE or EPR. The 20 °C value gives a smaller drop than the cable will really have under load.

What it does not cover

AC reactance and power factor on very large conductors.